Welcome to our online Request for Quote (RFQ) service, where you can fill out and submit the form provided below to obtain tailored procurement options from our team of industry experts. You have taken interest in part number THQC2160WL, which is a Circuitbreaker item from General Electric Company that is listed with the NSN 5925-00-728-6447 for quick identification. Should you wish to move forward with quotation for this listing, be sure that you supply us with key details like your target pricing, quality, and delivery date. This information is what we will base presented quotes on, with responses offered shortly after the receipt and review of each form.
Note : We Will Not Share Your Information To Any Third Parties.
To ensure that customers only procure exact items of need, we present our offerings with as much relevant data as possible. For example, part number THQC2160WL was specifically produced by General Electric Company under the CAGE Code 03497, providing traceability. Furthermore, with the NSN 5925-00-728-6447, one can also determine that this listing falls under Federal Supply Class (FSC) 5925 Circuit Breakers. Alongside such details, all purchases will come delivered with any applicable qualifying certifications, furthering the reliability of our purchasing options. With this in mind, be sure to request a quote on part number THQC2160WL, and we will be in touch.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-728-6447 Item PartTypeName: CIRCUIT BREAKER | 5925 | 007286447 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
THQC2160WL | 2 | 9 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
ADAU | BODY HEIGHT | 2.359 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.187 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 TERMINAL |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 60.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 3.875 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.000 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.000 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 18.000 MINIMUM AT 200 PCT AND 125.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CWJK | CASE MATERIAL | PLASTIC |
TTQY | TERMINAL TYPE AND QUANTITY | 2 CLIP AND 2 COMPRESSION |
If You’re Ever Looking for NSN parts Or Have an Aircraft On Ground Situation, Don’t forget That We offer Competitive Pricing and Guaranteed On-Time Delivery.